ESIE15-11A | Part 3. Field settings 9. Aircurtain CAV/CYV
Page 48 23/09/16
VRV4 indoor units
9. Aircurtain CAV/CYV
10. VKM
14/
24
6 Fan switching delay at hotstart in minutes 01 0 minutes (fan starts immediately)
02 1 minute
03 3 minutes (default)
04 5 minutes
7 Fan switching delay for hotstart in °C depending
on the condensing pressure
01 34°C
02 37°C
03 40°C
04 43°C (default)
8 Fan speed during defrosting or oil return 01 Fan off
02 Fan LL (default)
03 Keep fanspeed
15/
25
5 independent ventilation 01
not equipped
02 equipped
6 independent unit 01
no
02 yes