ESIE15-11A | Part 3. Field settings 6. General indoor units
Page 42 23/09/16
VRV4 indoor units
11 /
21
3 Fan setting of heating 01 standard
02 slight increase
03 increase
6 Sensitivity presence sensor 01 high sensitive for BRYQ140A7 / BRYQ60A
02 low sensitive
03
standard
04 disable presence sensor
7 External static pressure setting:
Automatic airflow adjustment function
01
airflow adjustment is OFF
(manual setting 23-6)
For FXSQ-FXMQ
1. Turn off the indoor unit
2. Set indoor unit to fan operation
mode.
3. Choose desired fanspeed (L,H,HH)
4. Change setting 21-7-00 to 21-7-03
and exit setting menu
5. Activate indoor unit to start the
learning function
6. Learn
02 Completion of automatic
airflow adjustment
03 Start of automatic airflow
adjustment
8 Compensation by floor sensor 01 floor sensor disabled for BRYQ140A7 / BRYQ60A
02 air suction temperature pri-
ority
03
standard
04 floor temperature priority
9 Compensation by floor temperature 01 -4°C for BRYQ140A7 / BRYQ60A
02 -2°C
03
no correction
04 +2°C