ESIE15-11A | Part 3. Field settings 11. FXSQ-A / FXNQ-A / FXDQ-A / FXMQ-P/MB / FXTQ-A
Page 52 23/09/16
VRV4 indoor units
FXSQ-A, FXMQ-P/M, FXTQ-A: specific settings
FXSQ-A FXMQ-M FXMQ-P FXTQ-A Comment
13/
23
6 External static
pressure (Pa)
01 30 Std ESP 30 Tbc ESP value based on nominal airflow
rate = Hhspeed
Possible available settings depend
on outdoor unit size (see corre-
sponding IM)
02 - High ESP 50 Tbc
03 30 60 Tbc
04 40 70 Tbc
05 50 80 Tbc
06 60 90 Tbc
07 70 100 Tbc
08 80 110 Tbc
09 90 120 Tbc
10 100 130 Tbc
11 110 140 Tbc
12 120 150 Tbc
13 130 160 Tbc
14 140 180 Tbc
15 150 200 Tbc
11/
21
7 Auto-adjust-
ment of ESP
01 Deactivated, manual through 13/23-6 / Only applicable for FXSQ and FXMQ
02 Auto-adjustment
03 Start auto-adjustment