Indoor Units • CONCEALED CEILING UNIT • FXSQ-P7VEB
1 Specifications
1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXSQ20P7VEB FXSQ25P7VEB FXSQ32P7VEB FXSQ40P7VEB FXSQ50P7VEB
Power Supply Name VE
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 0.4 0.4 0.4 1.2 1.2
Maximum fuse amps (MFA) A 16
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXSQ63P7VEB FXSQ80P7VEB FXSQ100P7VEB FXSQ125P7VEB
Power Supply Name VE
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 1.1 1.3 1.6 2.1
Maximum fuse amps (MFA) A 16
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXSQ20P7VEB FXSQ25P7VEB FXSQ32P7VEB FXSQ40P7VEB FXSQ50P7VEB
Power Supply Name VE
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 0.4 0.4 0.4 1.2 1.2
Maximum fuse amps (MFA) A 16
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXSQ63P7VEB FXSQ80P7VEB FXSQ100P7VEB FXSQ125P7VEB
Power Supply Name VE
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 1.1 1.3 1.6 2.1
Maximum fuse amps (MFA) A 16
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker