Indoor Units • CONCEALED CEILING UNIT • FXSQ-P7VEB
•VRV
®
Systems • Indoor Units
6
2 Electrical data
FXSQ-P
SYMBOLS
MCA: Min. Circuit Amps (A)
MFA: Max. Fuse Amps (A) (See note 4)
NOTES
1 Voltage range
The volts are suitable for use on electrical systems where the voltage
supplied to the unit terminals is not below or above listed range limits.
2 The maximum allowable voltage variation between phases is 2%.
3 Select a wire size based on the MCA.
4 Instead of a fuse, use a circuit breaker.
Units Power supply
Model Type Hz Volts Min. Max. MCA MFA
FXSQ20
VE 50/60
220~240V /
220V
-10% +10%
0.4
16
FXSQ25 0.4
16
FXSQ32 0.4
16
FXSQ40 1.2
16
FXSQ50 1.2
16
FXSQ63 1.1
16
FXSQ80 1.3
16
FXSQ100 1.6
16
FXSQ125 2.1
16
4TW31181-2