Loading...
Indoor Units • Concealed Ceiling Unit • FXSQ-MVE9
1
2
•VRV
®
Systems • Indoor Units
6
2 Safety device settings
3 Options
Safety devices FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ25MVE
FXSQ~MVE PC boad fuse 250V 10A 250V 10A 250V 10A 250V 10A 250V 10A 250V 10A 250V 10A
__________
250V 10A
Fan motor thermal fuse °C 152
±2
152
±2
152
±2
152
±2
152
±2
152
±2
__________ __________ __________
Fan motor thermal
protector
°C
Off: 130
±5
(On: 90
±15
)
Off: 130
±5
(On: 90
±15
)
Off: 130
±5
(On: 90
±15
)
__________ __________ __________
Off: 135
±8
(On: 87
±15
)
Off: 135
±8
(On: 87
±15
)
Off: 135
±8
(On: 87
±15
)
Drain pump thermal fuse °C 169 169 169 169 169 169 169 169 169
3D040447
FXSQ-MVE
No
Item Type FXS
~L
FXSQ
~MVE
1 Remote control
Wireless
H/P BRC4C62
C/O BRC4C64
Wired BRC1A62
2 Simplified remote control BRC2A51
3 Remote control for hotel use BRC3A61
4 Adaptor for wiring KRP1B61
5-1 Wiring adaptor for electrical appendices (1) KRP2A61
5-1 Wiring adaptor for electrical appendices (2) KRP4A51
6 Remote sensor KRCS01-1
7 Installation box for adaptor PCB.
note 5
KRP4A91
8 Central remote control DCS302C61
8-1 Electrical box with earth terminal (3 blocks) KJB311A
9 Unified on/off control DCS301B61
9-1 Electrical box with earth terminal (2 blocks) KJB212A
9-2 Noise filter
(for electromagnetic interface use only)
KEK26-1
10 Schedule timer DST301B61
11 External control adaptor for outdoor unit
(Must be installed on indoor units)
DTA104A61
3D034600C