IOM 1266-2 • MAGNITUDE
®
MODEL WME CHILLERS 42 www.DaikinApplied.com
operaTIon
Figure 56: Settings View - Valves
Table 17: Valve Setpoint Settings
Description Default Range PW Comments
EXV Gain 78 20-400 T Gain selection based on chiller size and valve type.
Figure 57: Settings View - Offsets
Table 18: Offsets Setpoint Settings
Description Default Range PW Comments
Evap EWT 0.0 -1.5 to 1.5 T
Sets the offset for the sensor listed based upon jobsite calibrations.
Evap LWT 0.0 -1.5 to 1.5 T
Cond EWT 0.0 -1.5 to 1.5 T
Cond LWT 0.0 -1.5 to 1.5 T
Liquid Line Temp 0.0 -1.5 to 1.5 T
Comp Discharge Temp 0.0 -1.5 to 1.5 T
Comp Suction Temp 0.0 -1.5 to 1.5 T
Evap Pressure 0.0 -2 to 2 T
Cond Pressure 0.0 -2 to 2 T
Liquid Line Pressure 0.0 -2 to 2 T
Comp Discharge Press 0.0 -2 to 2 T
Comp Suction Press 0.0 -2 to 2 T