Installation, Operation,
and Maintenance Manual
Trailblazer
®
Air-Cooled Scroll Compressor Chillers
󰀩

30 to 241 Tons (100 to 840 kW)

50/60 Hz
IOM 1206-13
Group: Chiller
Part Number: IOM1206-13
Date: September 2020

Questions and Answers

  • B
    brianna25Aug 14, 2025
    What causes overload relays or circuit breakers to open on a Daikin Trailblazer AGZ110-130E Chiller?
    • G
      Gregory HunterAug 14, 2025
      If the motor overload relays or circuit breakers are open in your Daikin Chiller, it could be due to a voltage imbalance or a voltage that is out of range, which requires correcting the power supply. Defective or grounded wiring in the motor necessitates replacing the compressor. Loose power wiring or burnt contactors require checking all connections, tightening them, and replacing the contactors if needed. High condenser temperature can also cause this issue, so refer to the corrective steps for high discharge pressure.
  • A
    Aaron PenaAug 20, 2025
    Why is the discharge pressure high in my Daikin Chiller?
    • A
      Alisha HillAug 20, 2025
      High discharge pressure in your Daikin Chiller can stem from several issues. Noncondensables in the system require extraction using approved procedures, or you may need to replace the charge. An overcharged circuit needs excess refrigerant removed, and liquid subcooling should be checked. Ensure the optional discharge shutoff valve is open. Incorrect condenser fan control wiring needs correction. If the fan isn't running, check the electrical circuit and fan motor. A dirty condenser coil requires cleaning, and air recirculation needs to be corrected.
  • C
    Christopher ThomasAug 25, 2025
    How to fix a noisy or vibrating Daikin Chiller compressor?
    • C
      cindykimAug 25, 2025
      If your Daikin Chiller's compressor is noisy or vibrating, several factors could be at play. Low lift or an inverted start might require control adjustments or condenser fan VFDs. Ensure the compressor isn't running in reverse by checking the unit and compressor for correct phasing. Improper piping or support on the suction or discharge lines may necessitate relocating, adding, or removing hangers. Worn compressor isolator bushings should be replaced. In cases of compressor mechanical failure, replacement is necessary.
  • M
    melinda82Sep 3, 2025
    Why won't my Daikin Chiller compressor stage up?
    • B
      Bianca AustinSep 3, 2025
      If your Daikin Chiller compressor will not stage up, it could be due to a defective capacity control, which would need replacing. Another cause may be a faulty sensor or wiring, which also requires replacement. It's also possible that the stages are not set for the specific application, in which case you should adjust the controller setting accordingly.
  • M
    Maria JohnsonSep 6, 2025
    What causes short compressor staging intervals in Daikin Trailblazer AGZ110-130E Chiller?
    • C
      carolyn88Sep 6, 2025
      If the compressor staging intervals are too short on your Daikin Chiller, the control band may not be set properly, requiring adjustment of the controller settings for the application. A faulty water temperature sensor should be replaced. Insufficient water flow requires correction. Rapid temperature or flow swings necessitate stabilizing the load. Oversized equipment may require evaluating the equipment selection. If the chiller is enabled with no load, evaluate the BAS sequence and settings. For light loads, evaluate the need for HGBP or thermal inertia.
  • M
    morajesseSep 10, 2025
    What does it mean if my Daikin Trailblazer AGZ110-130E Chiller's compressor thermal protection switch is open?
    • T
      Terry BarnesSep 10, 2025
      If the compressor thermal protection switch opens on your Daikin Chiller, it could be due to operating beyond design conditions, which requires correcting the conditions to stay within allowable limits. Ensure the discharge valve is open. Short cycling can also cause this, so stabilize the load or correct control settings for the application. Check and correct any voltage range or imbalance. High superheat requires adjustment to correct superheat. In some cases, compressor mechanical failure may be the cause, necessitating compressor replacement.
  • D
    Dr. Brenda MullinsNov 16, 2025
    How to troubleshoot Daikin Chiller compressor that will not run?
    • E
      Erin RobinsonNov 16, 2025
      If the compressor in your Daikin Chiller is not running, first, ensure that the main or compressor disconnect switch is closed. A blown fuse or open circuit breaker could also be the cause; inspect electrical circuits and motor windings for shorts or grounds, check for loose or corroded connections, and replace the fuse or reset the breakers after correcting the fault. Thermal overloads may have tripped; these are auto-reset, so check voltages, cycle times, and mechanical operations, allowing time for the auto-reset. A defective contactor or coil will need replacement. Also, check for system shutdowns triggered by equipment protection devices; identify the cause and correct it before restarting. If no cooling is required, simply wait until the unit calls for it. Other potential issues incl...
  • B
    Brian HernandezNov 26, 2025
    What to do if Daikin Chiller compressor oil level is too high or too low?
    • M
      Matthew StewartNov 26, 2025
      If the oil level in your Daikin Chiller's compressor is too high or too low, start by reviewing the refrigerant piping and correct any issues causing oil hang-up in remote piping. For a low oil level, verify superheat and add oil as needed. Repair any loose fittings on the oil line. If the level is too high while the compressor is running, confirm correct superheat and remove oil. Insufficient water flow can also cause a high oil level, so correct the flow and verify superheat. Excessive liquid in the crankcase can lead to a high oil level—check the crankcase heater and liquid line solenoid valve operation. Short cycling can affect oil levels, so stabilize the load or correct control settings. An oversize or improperly set-up HGBP valve should be replaced or adjusted. Evaluate expansion va...
  • K
    Kelly ReidDec 1, 2025
    Why is the suction pressure low in my Daikin Trailblazer AGZ110-130E?
    • C
      calvinjonesDec 1, 2025
      Low suction pressure in your Daikin Chiller can arise from various causes. Rapid load swings require stabilization. A lack of refrigerant necessitates checking for leaks, repairing them, and adding charge, along with inspecting the liquid sight glass. A fouled liquid line filter drier needs a pressure drop check and replacement if necessary. Malfunctioning expansion valves should be repaired or replaced and adjusted for proper superheat. Low condensing temperatures require checking the means for regulating condenser temperature. If compressors aren't staging properly, refer to corrective steps for compressor staging intervals that are too low. Insufficient water flow needs correction. Excess or the wrong oil requires recovery or change. A dirty evaporator should be back flushed or chemical...

Summary

Installation and Application Information

Electrical Data

Electrical Connection

Details electrical connection requirements, wiring, and safety precautions.

Unit Controller Operation

Set Points

Details the configurable set points for unit operation.

Sequence of Operation

Unit Sequence of Operation - Cool Mode

Describes the step-by-step process for chiller operation in cool mode.

Unit Sequence of Operation - Ice Mode

Explains the sequence of operation for the chiller in ice mode.

Circuit Sequence of Operation

Outlines the operational sequence for individual refrigerant circuits.

Unit Functions

Unit Capacity Control

Explains how the unit's capacity is managed and limited.

Compressor Staging in Cool Mode

Details how compressors are staged for optimal cooling performance.

Circuit Functions

Alarms

Evaporator Flow Loss

Describes the alarm triggered by a lack of evaporator flow.

Evaporator Water Freeze Protect

Explains the alarm for potential evaporator freezing.

Low Evaporator Pressure

Details the alarm for critically low evaporator pressure.

Using the Controller

Fan VFD Controller

Types of Alarms, Faults, and Errors

Categorizes and describes different types of drive alarms, faults, and errors.

Startup and Shutdown Procedures

Pre-Startup

Outlines essential checks before initiating chiller startup.

Pre-Startup Electrical Check Out

Details the critical electrical checks required before startup.

Startup

Provides instructions for the initial startup of the chiller.

Unit Maintenance

Troubleshooting Chart

Compressor Will Not Run

Addresses issues when the compressor fails to start.

Warranty Registration Form (Scroll)

Limited Product Warranty

Daikin Trailblazer AGZ110-130E Specifications