What causes overload relays or circuit breakers to open on a Daikin Chiller?
- TThomas HarringtonAug 14, 2025
If the motor overload relays or circuit breakers are open in your Daikin Chiller, it could be due to a voltage imbalance or a voltage that is out of range, which requires correcting the power supply. Defective or grounded wiring in the motor necessitates replacing the compressor. Loose power wiring or burnt contactors require checking all connections, tightening them, and replacing the contactors if needed. High condenser temperature can also cause this issue, so refer to the corrective steps for high discharge pressure.