www.DaikinApplied.com 27 OM 1085-6 • MICROTECH III CONTROLLER
4. Verify that the following are all selected from the screen
shown in Figure 58:
• State setting = Online
• Source of CP Values setting = Defaults and Include
NV type CPs
•
CPs
5. Click Next.
.
6. Verify that Service pin is selected and then click Finish
(Figure 59).
7. The screen in Figure 60 appears.
8. Press the service pin button on the
communication module. Refer to Figure 49 for the
location of the service button.
At this point, the application image starts loading the
communication module. This process takes
approximately one minute (Figure 61).
The MTIII WSHP device changes color to green which
indicates successful commissioning (Figure 62).
Communication Module –
Commissioned
In order to program another device, it is necessary
three steps:
1. Right click on the commissioned device
2. Select Commissioning
3. Left click on Decommission