6 | Technical data
Service manual
251
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
6.7 Field settings
6.7.1 To control heating only mode
Prerequisite: Stop operation of the unit.
1 Press
, , and simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 19.
7 Press
to confirm.
8 Press
.
9 Select 1 (0: factory setting, 1: heating only).
10 Press
to confirm.
6.7.2 To adjust target set temperature in heating operation
INFORMATION
When there is a big difference between the indoor room temperature and the set
temperature in heating mode, adjust the target set temperature field setting.
Target temperature = remote controller set temperature + 2.5°C. For
example:
Remote controller set temperature = 20°C
Target temperature = 20°C + 2.5°C = 22.5°C
Thermo off temperature = 24.5°C
1 Press
, , and simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 7.
7 Press
to confirm.
8 Press
.
9 Select the value to set the desired target temperature:
0 = –2,0°C
1 = –1,0°C
2 = 0°C (factory setting)
3 = +1,0°C
4 = +2,0°C
10 Press
to confirm.