3 | Components
Service manual
112
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
A Wall mounted indoor unit
a Connector S102
A Floor standing indoor unit
a Connector S102
Is the measured voltage on the indoor
unit power PCB correct?
Action
Yes Return to "Checking
procedures"[4110] of the indoor unit
power PCB and continue with the next
procedure.
No Replace the indoor unit power PCB, see
"Repair procedures"[4115].
To check if the correct spare part is installed
Prerequisite: First perform all earlier checks of the indoor unit main PCB, see
"Checking procedures"[4110].
1 Visit your local spare parts webbank.
2 Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.