3 | Components
Service manual
114
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a
A
A Wall mounted indoor unit
a Fuse F1U
aA
A Floor standing indoor unit
a Fuse F1U
Blown fuse on the indoor unit power
PCB?
Action
Yes Replace the blown fuse, see "Repair
procedures"[4115].
No Return to "Checking
procedures"[4102] of the indoor unit
power PCB and continue with the next
procedure.
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.