3 | Components
Service manual
194
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
Other refrigerant side thermistors
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "3.14Plate work"[4151].
6 Locate the thermistor that needs to be removed.
7 Remove the thermistor from the thermistor holder as follows:
For outdoor unit air (ambient) thermistor:
Open the thermistor holder and remove the thermistor from the holder.
For refrigerant piping thermistors:
- Cut the tie straps that fix the insulation and the thermistor wire.
- Cut and remove the insulation.
- Pull the clip that fixes the thermistor.
- Remove the thermistor from the thermistor holder.
c ba
a
f
d e
a Tie strap
b Insulation
c Thermistor wire
d Clip
e Thermistor
f Thermistor holder
8 Cut all tie straps that fix the thermistor harness.