3 | Components
Service manual
196
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
For outdoor unit air (ambient) thermistor:
Correctly install the thermistor in the holder and close the thermistor holder.
For refrigerant piping thermistors:
Pull the clip and install the thermistor in the specific thermistor holder. Make
sure the clip is in the correct position (blocking the thermistor).
c
a b
e df
f
a Clip
b Thermistor
c Thermistor holder
d Insulation
e Thermistor wire
f Tie strap
6 Route the thermistor harness towards the appropriate PCB.
7 Connect the thermistor connector to the appropriate PCB.
INFORMATION
Some of the thermistors are wired to the same connector. See connector and pin
information of the thermistors at the start of the electrical check procedure and
"6.2Wiring diagram"[4223]. ALWAYS replace the complete set of thermistors wired
to the same connector.
8 When installing the complete set of thermistors wired to the same connector: