3 | Components
Service manual
50
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
1 Turn OFF the respective circuit breaker.
2 Visually check:
For oil drops around the compressor. Locate and fix as needed.
Pipes for signs of damage. Replace pipes as needed.
3 Check that the compressor bolts are correctly fixed. Fix as needed.
4 Check that the compressor wire terminals cover is correctly installed and
fixed. Correct as needed.
5 Check the compressor dampers for any damage.
a
a
1 Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Action
Yes Perform an electrical check of the
compressor, see "Checking
procedures"[449].
No Replace the compressor, see "Repair
procedures"[455].
To perform an electrical check of the compressor
1 First perform a mechanical check of the compressor, see "Checking
procedures"[449].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10VDC before proceeding.
2 Remove the cover of the compressor wire terminals.