Daikin R410A - Outdoor Unit Clearance and Cable Sizing

Daikin R410A
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
TM-FVN-0515-A
Outdoor Clearance
Avoid installing or operating the condensing unit in the environment that is exposed to the
following substances:
Oils (including machine oils)
Salt (e.g. coastal area)
Sulphide gas (e.g. hot spring areas, oil refinery plant, etc)
Such substances may lead to the failure of the unit.
A
AIR INLET
AIR DISCHARGE
B
OBSTACLE
OBSTACLE
C
AIR INLET
SERVICE SPACE
D
OBSTACLE
OBSTACLE
ALL MODELS
Minimum Distance
A
300 mm
B
1000 mm
C
300 mm
D
500 mm
Cable Size
Model Unit
FVN30AV1L
RN28CV1
Power supply cable size
Number of wire
mm
2
2.5
3
1.5
5
Interconnection cable size
Number of wire
mm
2
2.5
4
1.0
4
0223AesufdednemmoceR
Model Unit
FVN50AV1L
RN50DY1
Power supply cable size
Number of wire
mm
2
1.5
5
1.5
5
Interconnection cable size
Number of wire
mm
2
1.0
4
1.0
4
5252AesufdednemmoceR
FVN60AV1L
RN61DY1
FVN40AV1L
RN40DY1