Troubleshooting by Indication on the Remote Controller Si39-302
180 Troubleshooting
2.20
F3
Outdoor Unit: Abnormal Discharge Pipe
Temperature
Remote
Controller
Display
F3
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
!
When the discharge pipe temperature rises to an abnormally high level
!
When the discharge pipe temperature rises suddenly
Supposed
Causes
!
Faulty discharge pipe temperature sensor
!
Faulty connection of discharge pipe temperature sensor
!
Faulty outdoor unit PCB
Troubleshooting
2: Refer to thermistor resistance / temperature characteristics table on P280.
(V3068)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Discharge pipe
temperature is 115˚C
or higher.
Are
the characteristics
of the discharge pipe
thermistor normal?
(3.5~400K)
Replace outdoor unit PC board
A2P.
Replace the discharge pipe
thermistor.
NO
NO
Out of gas, compression defect,
etc. Defect of the refrigerant
system.
YES
YES