Basic Control SiBE37-701_B
109 Function
Operating Priority and Rotation of Compressors
Each compressor operates in the following order of priority.
In the case of multi-outdoor-unit system, each compressor operates in any of Pattern 1
through Pattern 3 according to the rotation of outdoor units.
Pattern 1 Pattern 2 Pattern 3
INV: Inverter compressor
STD1: Standard compressor 1
STD2: Standard compressor 2
REYQ8P, 10P, 12P REYQ14P, 16P
No. 2 No. 1
STD1 INV
No. 2 No. 1
INV2 INV1
REYQ18P, 20P REYQ22P, 24P
No. 1
No. 2 No. 3
No. 1 No. 3 No. 2 No. 4
No. 1 No. 3
No. 2 No. 4 No. 1 No. 3
No. 2
INV INV STD1 INV STD1INV STD1
REYQ26P, 28P REYQ30P, 32P
No. 1 No. 3 No. 2 No. 4 No. 5
No. 1 No. 3 No. 5 No. 2 No. 4 No. 6
No. 2 No. 4 No. 1 No. 3 No. 5
No. 2 No. 4 No. 6 No. 1 No. 3 No. 5
INV STD1 INV STD1 STD2 INV STD1 STD2 INV STD1 STD2
REYQ34P, 36P
No. 1 No. 2 No. 4 No. 3 No. 5 No. 6
No. 3 No. 1 No. 4 No. 2 No. 5 No. 6
No. 2 No. 3 No. 5 No. 1 No. 4 No. 6
INV INV STD1 INV STD1 STD2