Outline of Control (Indoor Unit) SiBE37-701_B
147 Function
6.3 Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure
below).
6.3.1 When the Float Switch is Tripped while the Cooling Thermostat is
ON:
1. (Normal operation):
The objective of residual operation is to completely drain any moisture adhering to the fin of the
indoor unit heat exchanger when the thermostat goes off during cooling operation.
2. (Malfunction residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop in 5
minutes if the float switch is turned OFF while the cooling thermo. is ON.
6.3.2 When the Float Switch is Tripped while the Cooling Thermostat is
OFF:
*3. (Malfunction residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop if
the float switch is turned OFF and not turned ON again within 5 minutes while the cooling
thermo. is OFF.
Thermostat
(running)
Float switch
Drain pump
ON
OFF
ON
OFF
ON
OFF
Remote controller "A3" flashing
malfunction stop
5 min. 5 sec.5 min.
*1) Normal operation *2) Malfunction residual
Thermostat
(running)
Float switch
Drain pump
ON
OFF
ON
OFF
ON
OFF
5 min.
5 sec.
5 min.
5 sec.
Enters malfunction treatment if the float switch is not reset within 5 minutes.
Remote controller "A3" flashing malfunction stop
*3