SiBE37-701_B Outline of Control (Indoor Unit)
Function 146
6.2.4 Thermostat Control with Operation Mode Set to "AUTO"
When the operation mode is set to "AUTO" on the remote controller, the system will conduct the
temperature control shown below.
Furthermore, setting changes of the differential value (D°C) can be made according to
information in the "Field settings with remote controller (p. 191 and later)" section.
: Factory setting
Mode
No.
First code
No.
Contents of setting
Second code No.
01 02 03 04 05 06 07 08
12 4
Differential value while in "AUTO"
operation mode
0°C 1°C C 3°C C 5°C 6°C 7°C
Set heating temperature
(A-D)°C
D°C
Set cooling temperature
A°C
Cooling thermostat ON
Cooling thermostat OFF
Heating thermostat OFF
Heating thermostat ON
Display change
Cooling
Heating
Display change
Cooling
Heating
3°C
( +2)°C
D
2
(Ex.) When automatic cooling temperature is set to 27°C:
Differential value :0°C
Set cooling/
heating temp.
25°C
27°C
30°C
Cooling mode
Control temp.
Heating mode
Differential value :0°C
Set heating temp.
23°C
26°C
Cooling mode
Control temp.
Heating mode
Differential value set to 4°C
22°C
Cooling mode
Control temp.
Heating mode
Differential value set to 5°C
Set heating temp.
24.5°C
26°C
29°C
Cooling mode
Control temp.
Heating mode
Differential value set to 1°C
Set heating temp.
24°C
25°C
Cooling mode
Control temp.
Heating mode
Differential value set to 2°C
Set heating temp.
23.5°C
24°C
Cooling mode
Control temp.
Heating mode
Differential value set to 3°C
22°C
27°C
Cooling mode
Control temp.
Heating mode
Differential value set to 6°C
Set heating temp.
21.5°C
20°C
Cooling mode
Control temp.
Heating mode
Differential value set to 7°C
Set heating temp.
Set cooling temp.
27°C
Set cooling temp.
27°C
Set heating temp. Set cooling temp.
27°C
22.5°C
25°C
Set cooling temp.
27°C
28°C
Set cooling temp.
27°C
Set heating temp.
21°C
Set cooling temp.
24°C
Set cooling temp.
27°C
23°C

Table of Contents