Special Control SiBE37-701_B
125 Function
Cooling indoor unit actuator Oil return operation
Fan
Thermo. ON unit Remote controller setting
Unit not in operation OFF
Thermo. OFF unit Remote controller setting
Electronic expansion
valve
Thermo. ON unit Normal opening degree
Unit not in operation 192pls
Thermo. OFF unit Normal opening degree for forced thermostat ON
Heating indoor unit actuator Oil return operation
Fan
Thermo. ON unit Remote controller setting
Unit not in operation OFF
Thermo. OFF unit Remote controller setting
Electronic expansion valve
Thermo. ON unit Normal opening degree
Unit not in operation 224 pls
Thermo. OFF unit Normal opening degree for forced thermostat ON
Cooling BS unit actuator Elect. symbol Oil return operation
Electronic expansion valve (EVH) Y4E 0pls
Electronic expansion valve (EVL) Y5E 760pls
Electronic expansion valve (EVHS) Y2E 0pls (60pls when Pc
_
max>2.85MPa)
Electronic expansion valve (EVLS) Y3E 480pls
Electronic expansion valve (EVSC) Y1E PI control
Heating BS unit actuator Elect. symbol Oil return operation
Electronic expansion valve (EVH) Y4E 760pls
Electronic expansion valve (EVL) Y5E 0pls
Electronic expansion valve (EVHS) Y2E 60pls
Electronic expansion valve (EVLS) Y3E 0pls (60pls when Pc
_
max>2.85MPa)
Electronic expansion valve (EVSC) Y1E PI control