SiBE37-701_B Field Setting
Test Operation 194
3.1.3 Simplified Remote Controller
BRC2A51
BRC2C51
1. Remove the upper part of remote controller.
2. When in the normal mode, press the [BS6] BUTTON () (field set), and the FIELD SET
MODE is entered.
3. Select the desired MODE No. with the [BS2] BUTTON () (temperature setting
) and the
[BS3] BUTTON () (temperature setting
).
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been
selected), push the [BS8] () BUTTON (unit No.) and select the INDOOR UNIT NO. to be
set. (This operation is unnecessary when setting by group.)
5. Push the [BS9] BUTTON () (set A) and select FIRST CODE NO.
6. Push the [BS10] BUTTON () (set B) and select SECOND CODE NO.
7. Push the [BS7] BUTTON () (set/cancel) once and the present settings are SET.
8. Push the [BS6] BUTTON () (field set) to return to the NORMAL MODE.
9. (Example) If during group setting and the time to clean air filter is set to FILTER
CONTAMINATION - HEAVY, SET MODE NO. to “10”, FIRST CODE NO. to “0”, and
SECOND CODE NO. to “02”.
MODE NO.
UNIT NO.
FIRST
CODE NO.
SECOND
CODE NO.
(V0294)
(7) (4) (5) (6)(2)(8)
(3)
(3)