Field Setting SiBE37-701_B
219 Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
24
ENECUT test
operation (Domestic
Japan only)
khkkhhh
ENECUT output OFF
khhhhhk
∗
ENECUT output forced ON
khhhhkh
25
Setting of external
low noise level
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
∗
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Night-time low noise
operation start
setting
khkkhkh
About 20:00
khhhhhk
About 22:00 (factory setting)
khhhhkh
∗
About 24:00
khhhkhh
27
Night-time low noise
operation end setting
khkkhkk
About 6:00
khhhhhk
About 7:00
khhhhkh
About 8:00 (factory setting)
khhhkhh
∗
28
Power transistor
check mode
khkkkhh
OFF
khhhhhk
∗
ON
khhhhkh
29
Capacity
precedence setting
khkkkhk
OFF
khhhhhk
∗
ON
khhhhkh
30 Demand setting 1
khkkkkh
60 % demand
khhhhhk
70 % demand
khhhhkh
∗
80 % demand
khhhkhh
32
Normal demand
setting
kkhhhhh
OFF
khhhhhk
∗
Demand 1
khhhhkh
Demand 2
khhhkhh
38
Emergency
operation (Master
unit is inhibited to
operate.)
kkhhkkh
OFF
khhhhhk
∗
Master unit operation: Inhibited
khhhhkh
39
Emergency
operation (Slave unit
1 is inhibited to
operate.)
kkhhkkk
OFF
khhhhhk
∗
Slave unit 1 operation: Inhibited
khhhhkh
40
Emergency
operation (Slave unit
2 is inhibited to
operate.)
kkhkhhh
OFF
khhhhhk
∗
Slave unit 2 operation: Inhibited
khhhhkh
41
Prevention of minute
heating operation by
heating thermostat
OFF unit or non-
heating-operation
unit
kkhkhhk
OFF
khhhhhh
Non-heating-operation unit
khhhhhk
Heating thermostat OFF unit
khhhhkh
Non-heating-operation + Thermostat OFF unit
khhhhkk
∗
42
Setting of BS Cool-
Heat selection
control time
kkhkhkh
6 min.
khhhhhh
∗
4 min.
khhhhhk
51
Master-slave set-up
for multi outdoor
units
kkkhhkk
Automatic judgment
khhhhhh
∗
Master
khhhhhk
Slave 1
khhhhkh
Slave 2
khhhhkk
The numbers in the "No." column represent the number of times to press the SET (BS2) button.