SiBE37-701_B Troubleshooting by Remote Controller
Troubleshooting 250
6.Error Display
Selection
1.Warning display ON Displays a warning on the screen if an error
occurs.
2. Warning display OFF No warning is displayed.
3.Error display ON Displays the error on the screen.
4.Error display OFF Displays neither errors nor warnings.
7.Unit No. Transfer 1. Current Unit No. A unit No. can be transferred to another.
2.Transfer Unit No.
8. Sensor Address
Display
{ Unit No.: 0 - 15 Select the Unit No. you want to check.
{
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
Remote controller thermistor (°C)
Suction air thermistor (°C)
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
BS unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
{
Data The corresponding data will be displayed, based
on the Unit No. and Code selected.
Service Menu Item 2 Remarks