Precautions for New Refrigerant (R-410A) SiBE37-701_B
461 Precautions for New Refrigerant (R-410A)
2. Torque wrench
Specifications
Dimension B Unit:mm
No change in tightening torque
No change in pipes of other sizes
Differences
Change of dimension B
Only 1/2", 5/8" are extended
3. Vacuum pump with check valve
Specifications
Discharge speed
z
Maximum degree of vacuum
50 l/min (50Hz) Select a vacuum pump which is able to keep
60 l/min (60Hz) the vacuum degree of the system in excess of
Suction port UNF7/16-20(1/4 Flare) –100.7 kPa (5 torr – 755 mmHg).
UNF1/2-20 (5/16 Flare) with adaptor
Differences
Equipped with function to prevent reverse oil flow
Previous vacuum pump can be used by installing adaptor.
Nominal size Class-1 Class-2 Previous
1/2 24
26 24
5/8 27
29 27
For class-1: R-407C
For class-2: R-410A
Dimension B
Vacuum pump adaptor
Reverse flow preventive
vacuum adaptor