Control Specification SiENBE04-808_A
45 Function and Control
3. Control Specification
3.1 Mode Hierarchy
Outline There are two modes; the one is the normal operation mode and the other is the forced
operation mode for installation and providing service.
Detail For Cooling Only Model
There are following modes; stop and cooling (including drying).
For Heat Pump Model
There are following modes; stop, cooling (includes drying), heating (include defrosting)
Note: Unless specified otherwise, an indoor dry operation command is regarded as cooling operation.
Air conditioner control mode
Forced operating mode
Forced cooling (for Pump Down Operation)
Normal operating mode
Cooling
Stop mode (except for cooling modes by indoor command)
Preheating operation
During C (capacitor) is discharging
Stop
(R2830)
Air conditioner control mode
Forced operating mode
Forced cooling (for Pump Down Operation)
Normal operating mode
Cooling
Heating
Defrosting
Stop mode (except for cooling/heating modes by indoor command)
Preheating operation
During C (capacitor) is discharging
Stop
(R2829)
SiENBE04-808_A.pdf 57 21/02/2011 13:19:56

Table of Contents

Other manuals for Daikin RKS20J2V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RKS20J2V1B and is the answer not in the manual?

Daikin RKS20J2V1B Specifications

General IconGeneral
BrandDaikin
ModelRKS20J2V1B
CategoryHeat Pump
LanguageEnglish

Related product manuals