Outdoor Unit - 80/90 Class SiBE121021_C
418 Removal Procedure
4
Disconnect the
connector for the four
way valve coil [S80].
îš„
Pull out the clamp.
îš„
The cooling only model has
no harness for [S80].
5
Disconnect the
connectors for the
electronic expansion
valve coil.
[S20] (white): room A
[S21] (red): room B
[S22] (blue): room C
[S23] (yellow): room D
îš„
Pull out the clamp.
îš„
5 room models also has
[S24] (green) for room E.
6
Disconnect the
connector for the liquid
pipe thermistor [S93].
îš„
Pull out the clamp.
Step
Procedure Points
[S80]
Clamp
(R11187)
A
B
C
D
Clamp
(R11188)
Clamp
[S93]
(R10400)