Page | 45
Alarm
Phase Voltage Protection Circuit
Code: UnitOffPhaseVoltage
OffNormal
Category:
Critical
Trigger
Action
Unit immediate shutdown
Reset method
Manual reset
Reset
Condition
Phase protector contact (NC) = Close for 5 Sec
Solution
Check unit power supply quality
Alarm
No
Yes
Yes
No
Main controller has power
up for 5 sec?
Phase protector contact
= Open?
Phase protector
configuration is “Single
point”?
Yes
No