68 | P a g e
Alarm
C#Cmp# Off Oil Feed Pressure
Sensor Fault
Code: C#Cmp#OilFeedPFault
Category:
Critical
Trigger
Action
Unit immediate shutdown
Reset method
Manual reset
Reset
Condition
Oil pressure in operating range
Solution
Check sensor condition, wiring and connector condition.
Alarm
C#Cmp# Off Suction Temp. Sensor
Fault
Code: C#Cmp#OffSuctTempFault
Category:
Critical
Trigger
Action
Unit immediate shutdown
Reset method
Manual reset
Reset
Condition
Suction temperature in operating range
Solution
Check sensor condition, wiring and connector condition.
Yes
No
Oil pressure = out of range?
Alarm
Yes
No
Suction temp = out of range?
Alarm