8
< Replacing the drain hose and drain plug >
(1) Remove the drain plug and insulation tubing.
(2) Remove the drain hose and replace onto the left side.
(3) Replace the drain plug and the insulation tubing onto the right side.
(6) Hook the indoor unit onto the installation panel. (Refer to Fig. 9)
• Placing buffering material between the wall and the indoor unit at this time will make work easier.
For right, bottom-right, and back-right piping
• Pass the drain hose and the refrigerant piping to the wall.
(7) Pass power supply wiring, transmission wiring, earth wiring, and remote controller wiring through
the wiring guide in through the back of the indoor unit and to the front.
Drain plug
Insulating tube
Fig. 8
Do not place lubricant (refrigerant oil) when inserting.
This may cause deterioration and water leaks.
Insert using a hexagon wrench (4mm).
Make sure
there are
no gaps.
Service cover
Refrigerant piping
Be sure to pass all wires through
the wiring guide.
Tab
(There are 2 places.)
Wiring (locally procured)
Power supply wiring, Transmission wiring, Earth wiring,
Remote controller wiring
Wall
Installation panel
(accessory) (1)
Front grille
Place buffering material
Fig. 9
Front panel
Hook the indoor unit hook onto the installation panel (1).