Daikin VRV IV RXYQ TYDN Series - 4.1.2 Equivalent Piping Length of Joints and Headers (Reference)

Daikin VRV IV RXYQ TYDN Series
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDUS341411-N REFNET Pipe System
Installation of Outdoor Units 55
4.1.2 Equivalent Piping Length of Joints and Headers (Reference)
* When the equivalent piping length in cooling operation is calculated, the gas pipe size is selected.
When the equivalent piping length in heating operation is calculated, the liquid pipe size is selected.
Pipe Size *
1/4 in.
(
6.4 mm)
3/8 in.
(
9.5 mm)
1/2 in.
(
12.7 mm)
5/8 in.
(
15.9 mm)
3/4 in.
(
19.1 mm)
7/8 in.
(
22.2 mm)
1 in.
(
25.4 mm)
1-1/8 in.
(
28.6 mm)
1-1/4 in.
(
31.8 mm)
1-3/8 in.
(
34.9 mm)
1-1/2 in.
(
38.1 mm)
1-5/8 in.
(
41.3 mm)
L Joints
6-1/4 in.
(0.16 m)
7-1/8 in.
(0.18 m)
7-7/8 in.
(0.20 m)
9-7/8 in.
(0.25 m)
13-3/4 in.
(0.35 m)
15-3/4 in.
(0.40 m)
17-3/4 in.
(0.45 m)
19-5/8 in.
(0.50 m)
21-5/8 in.
(0.55 m)
23-5/8 in.
(0.60 m)
25-5/8 in.
(0.65 m)
29-1/2 in.
(0.75 m)
REFNET Joint
1.6 ft (0.5 m)
REFNET Header
3.3 ft (1.0 m)