16 | Unit installation
Installer and user reference guide
46
FXMQ-A
VRV system air conditioner
4P701548-1 – 2022.07
Pipe size. Keep the pipe size equal to or greater than that of the connecting pipe
(vinyl pipe of 25mm nominal diameter and 32mm outer diameter).
Slope. Make sure the drain piping slopes down (at least 1/100) to prevent air
from being trapped in the piping. Use hanging bars as shown.
1~1.5 m
a
a Hanging bar
Allowed
Not allowed
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
Combining drain pipes. It is possible to combine drain pipes. Use drain pipes and
T-joints with the correct gauge for the operating capacity of the units.
≥100
a a
a T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
a
b
a Drain pipe connection
b Refrigerant pipes
Drain piping connection
1 Pull out the drain plug.
2 Install the adapter for the drain hose (field supply).
3 Push the drain hose as far as possible over the adapter for the drain hose.
4 Tighten the metal clamp until the screw head is less than 4 mm from the
metal clamp part.
5 Check for water leaks (see "To check for water leaks"[447]).
6 Install the insulation piece (drain pipe).