Si30-408 Adaptors for Connection of Air Conditioners
Appendix 203
2. Setting of CONTROL MODE selector switch (RS1)
To use the system only for display function only in individual display mode
To operate the system using constant input to the input A
Caution The input B is used for forcedly OFF. If this input B is turned ON, the system will be put into
“Stop + Remote controller inhibited”, thus disregarding the input A. Even if the input A is turned
ON with the input B in an OFF state, the content with the input A turned ON will not be provided.
In this case, the input A should be turned ON again.
To operate the system using instantaneous input to the input A
(Use instantaneous input with ON time of 200 msec or more for the input A.)
To conduct demand control using input B
Forcedly thermostat OFF command
This command is used to operate the indoor unit only in forcedly fan mode.
Energy saving operation command (*)
This command is used to operate the system with set temperature increased by 2°C in
cooling operation or decreased by 2°C in heating operation.
Caution
In this case, even though the input A is turned ON, the system will make a stop, thus
stopping all units in one and the same group.
* On the SkyAir series, even though Position D or F is selected, the forcedly thermostat OFF
command will be issued.
Position Function
0 Individual display (with input ignored)
Use the CONTROL MODE selector switch (RS1)
to make selection and setting of control mode
through input A or B.
Position Function Contents with input A tuned ON
Contents with input
A turned OFF
1
Remote controller
inhibited
Operation (The remote controller is inhibited
at all times.)
Stop + Remote
controller inhibited
2 Centralized priority Operation + Remote controller permitted
3
Remote controller
stop permitted
Operation + Only remote controller stop
permitted
(Operation from remote controller is
disabled.)
4
Remote controller
permitted / stop
Remote controller permitted
(Operation from remote controller is
impossible.)
Position Function Contents of input A Function of input B
5
Remote
controller
inhibited
Stops if the input A is turned ON while in
operation.
Operates if the input A is tuned ON while in stop.
The input B will be
put into forcedly
OFF function mode.
(If the input B is
turned ON, the
system will be put
into “Stop + Remote
controller inhibited,
Input A
disregarded”.)
6
Last-pressing
priority
Stops if the input A is turned ON while in
operation.
Operates if the input A is tuned ON while in stop.
(The remote controller is permitted at all times.)
Position Functions & contents with input A turned ON Functions with input B turned ON
C
Remote controller inhibited
(Same as Position 5)
Forcedly thermostat OFF command
D Energy saving operation command (*)
E
Last-pressing priority
(Same as Position 6)
Forcedly thermostat OFF command
F Energy saving operation command (*)