Adaptors for Connection of Air Conditioners Si30-408
204 Appendix
To operate the system on two input contacts using instantaneous input for the input
A and input B
(Use instantaneous input with ON time of 200 msec or more for the input A.)
Cautions
Using normal input for the input B in Positions 7 to A will put the system into forcedly stop
function (with input A disregarded).
In Position B, the normal input cannot be used for the input B.
3. Input of temperature settings
Temperature settings corresponding to resistance values in the range of 0 to 135Ω can be
made.
Caution The resistance values are counted in wiring resistance.
Position Function Contents of input A Contents of input B
7
Remote controller
inhibited
Operation (The remote controller is
inhibited at all times.)
Stop + Remote
controller inhibited
8 Centralized priority
Operation + Remote controller
permitted
9
Remote controller stop
permitted
Operation + Only remote controller stop
permitted
(Operation from remote controller is
impossible.)
A
Remote controller
permitted / stop
Only remote controller permitted
(Operation from remote control is
impossible.)
B Last pressing priority
Operation (The remote controller is
permitted at all times.)
Stop (The remote
controller is permitted
at all timed.)
NEVER apply voltage to terminal
A
+
or A
-
.
In order to make temperature settings from both remote and remote
controllers, set this switch to "Permitted". (Factory set: Permitted)
Permitted: Use this mode to make temperature settings from both remote
and remote controllers. (Last setting priority control is enabled.)
Inhibited: Use this mode only to make temperature settings from the
remote. (No temperature settings are enabled from the remote
controller.)
Set temp. (°C) 16 17 18 19 20 21 22 23 24
Resistance value
(Ω)
0.0~3.4
5.0~
11.6
13.8~
20.0
22.4~
28.4
31.0~
36.4
39.4~
44.8
48.2~
52.8
56.6~
61.2
65.2~
69.4
Set temp. (°C) 25 26 27 28 29 30 31 32
Resistance value
(Ω)
73.8~
77.8
82.4~
85.8
91.0~
94.0
99.4~
102.2
108.6~
110.4
117.2~
119.2
125.8~
127.4
134.2~
140.0
(Wiring specifications)
Types of wires ... Sheathed vinyl cords
Size of wire ... 1.25 to 2.00 mm
2
Total length of wiring ... 70 m at maximum
(Caution)
In order to prevent malfunctions, isolate this wiring from the power lines.