Field Settings from Remote Controller Si30-408
50 Field Settings from Remote Controller
Mode No. Function Contents and setting methods
Example of display on remote
controller
40
Display of malfunction
code history
Displays malfunction history.
The history No. can be changed with the
button.
41
Display of sensor data
and display of address
data
Displays various types of data.
Select the data to be displayed with the
button.
Sensor data
0: Remote controller thermostat
1: Suction
2: Liquid pipe
3: Gas pipe
Address data
4: Indoor unit address
5: Outdoor unit address
6: BS unit address
7: Zone control address
8: Cooling/heating batch address
9: Demand/low noise address
Unit
Malfunction code
2-U4
40
Malfunction code
History No: 1-9
1: Latest
1
27
41
Temperature ˚C
1 1
1
41
1 8
Address
Example of sensor data display
Unit No.
Type of address
Unit No.
Type of sensor
Example of address display