EasyManua.ls Logo

Daikin VRV - Wiring installation; WIRING EXAMPLES; Complete system example (3 systems); PRECAUTIONS

Daikin VRV
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Key Points for Selection
Obtain Project Data
Before selection of any VRV system, a minimum amount of information
is required for accurate equipment selection and to apply an
optimized design
For an accurate selection of indoor units the following information is required:
For an accurate selection of outdoor units the following information is required:
PEAK
Cooling Loads
PEAK
Heating Loads
DESIGN AIR
Conditions
» Engineers will
usually provide
both Total &
Sensible loads
which should
be entered
» However it is
possible to select
equipment using
only Total or
Sensible load
» Required when
either Heating
is the dominant
operation or the
heating design
condition is
below 32°F
» The dry & wet bulb
temperature entering
the coil
» Also known as
“air-on” or “mixed air”
conditions
» Nominal conditions are
typically 80 °F db &
67 °F wb but rarely
reflect actual conditions
» Design air-on can also
be given as db/RH%
(e.g. 74°F & 50% RH)
AMBIENT Conditions PIPE LENGTH
» The design ambient
temperature for the
location of the project
» Both engineers and D&B
contractors should have
this information
» If this information is not at
hand then use ASHRAE
standard design conditions
for the location
» The estimated distance between
the outdoor unit and the furthest
indoor unit
» This is the linear length from one
point to another NOT the total
amount of piping
» Both engineers and D&B
contractors should be able to pin
point the outdoor unit location
» Be sure to calculate and include
the vertical height between
outdoor & furthest indoor unit

Other manuals for Daikin VRV

Related product manuals