SIMULTANEOUS
VIA extended capacity tables
VIA technical cooling function
Cooling operation for VRV IV Heat Pump single
module systems (RXYQ72/96/120/144/168T) can be
extended down to 10˚F, from the standard limitation
of 23˚F under defined conditions.
Contact your local Daikin manufacturer’s
representative or distributor for details
.
A
C
H
E
G
B
F
D
16
Communication Wiring should be 18-2AWG stranded, no polarity,
no shielding
maximum linear distance = 3280ft, maximum total distance = 6560ft
» Maximum linear distance in the example below is the
longest of either
» (A) to (C), (A) to (E), (A) to (G) or (C) to (G)
» Maximum total distance is (A to F) + (B to C) + (D to E) + (F to G)
» Each local controller (H to C) can run up to a distance of 1640ft
Application Limits
Wiring Parameters
Ambient Limits