Piping and Electrical Wiring Guide
Power Wiring
1. Incoming Power from Mains
3PH4W 480 V or 208/230V
2. Disconnecting Means
3. Outdoor Unit
4. Fuse or Circuit Breaker
5. Branch Selector Box
6. Indoor Unit
Wiring ODUs in series to
a single CB is NOT an
acceptable conguration
1
2
3
5
4
6
2"
*Allow at least 2”
spacing between
control and line
level power
conductors to
prevent signal
distortion
Wiring IDUs in series to a single
CB IS an acceptable conguration
*NEC requires all IDU Fan Coils be connected to a 15A fuse braeker by default, though multiple
can be connected to the same circuit. The chart below can be used to determine the amount
of units that can be strung together.
.
Indoor Unit Model
Size (BtUh)
21
FXZQ
FXUQ
FXEQ
FXDQ
FXMQ-PB
FXMQ-M
FXAQ
FXHQ
FXLQ
FXTQ-TA
FXSQ
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
FLA
MCA
5 0.6 0.8
7
0.2
0.3
0.2
0.2
0.2
0.3
0.2
0.3
0.7
0.9
0.5
0.6
0.3
0.4
0.6
0.8
9 0.2 0.3 0.2 0.3 0.3 0.4 0.7 0.9 0.5 0.6 0.3 0.4 3.9 4.9 0.6 0.8
12
0.2
0.3
0.3
0.4
0.3
0.4
0.7
0.9
1.1
1.4
0.3
0.4
0.6
0.8
0.4
0.5
3.9
4.9
0.7
0.8
15
0.3
0.4
0.3
0.4
0.4
0.5
1.2
1.5
1.2
1.4
18
0.5
0.6
0.5
0.6
0.5
0.6
0.4
0.5
1
1.3
1.3
1.6
0.4
0.5
0.5
0.6
3.9
4.9
1.3
1.6
24 0.5 0.7 0.5 0.6 0.5 0.7 1.1 1.4 1.4 1.8 0.5 0.6 0.8 1 0.5 0.6 3.9 4.9 1.4 1.8
30 1 1.3 1.1 1.4 2.2 2.3 3.9 4.9 1.5 1.8
36 1.2 1.5 1.1 1.4 2.3 2.9 1.1 1.4 3.9 4.9 2 2.5
42
5.2
6.5
48 1.4 1.8 2.7 3.4 5.2 6.5 2 2.8
54
2.7
3.4
6.9
8.6
2.6
3.3
60 6.9 8.6
72
7.6
9.5
96 8.6 10.7
0.3