EasyManua.ls Logo

Daikin VRV - Page 39

Daikin VRV
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
Typically Daikin equipment has been applied using a standard rule of
thumb that a maximum of 20% OA can be incorporated into a ducted
fan coil unit (FXMQ, FXSQ, FXDQ and FXNQ). However, this practice
is not always applicable as this rule of thumb is based upon introducing
OA at nominal conditions.
Basic Rules
1. COOLING: Any percentage of OA can be used as long
as the resulting mixed air is between 57 and 77˚FWB
and 80% RH or lower.
2. HEATING: Any percentage of OA can be used as long
as the resulting mixed air is between 59 and 80˚FDB
and 80% RH or lower.
Note: Space temperature sensing should be done via the room zone controller or
remote sensor kit if a “mixed air” approach is taken.

Other manuals for Daikin VRV

Related product manuals