VLT
®
5000 Series
This parameter initialises all except:
500 Serial communication address
501 Baud rate for serial communication
601-605 Operating data
615-617 Fault logs
Manual initialisation
Disconnect from mains and wait until the
display turns off.
Press the following keys at the same time:
[Display/status]
[Change data]
[OK]
Reconnecting the mains supply while
pressing the keys.
Release the keys
The frequency converter has now been
programmed for the factory setting
.
This parameter initialises all except:
600-605 Operating data
NB!:
Settings for serial communication and
fault logs are reset.
MG.51.A9.02 - VLT is a registered Danfoss trademark
72