8.2 a³ Unit
Dimensions
Outdoor air
Exhaust air
Extract air
Supply air
Weight of unit: 67 kg
Front view (without front panel)
Filter, extract air
Filter, supply air
Flow chart (for balancing)
Filter reset button
Differential pressure for extract air
Differential pressure for supply air
Capacity Temperature ratio
Pressure [Pa] η [%]
40%
56%
82%
100%
1000 J/m³
300
250
200
150
100
50
0
0 50 100 150 200 250 300 350 400 450 500 550 600
*0.45 W/m³/h
Flow [m³/h]
80%
81%
82%
83%
84%
85%
86%
87%
88%
89%
90%
0 50 100 150 200 250 300 350 400 450 500
Flow [m³/h]
* 0.45 W/m³/h = "Passiv Haus" requirements.
Flow [m³/h] Pext. [Pa] SFP [J/m³] P
1
tot. [W]
200 70 787 44
350 70 835 81
450 70 973 122
350 100 1000 97
Tab. 6: Capacity for the a³ unit
Extract air Fresh air
t = 21 °C RH = 36% t = -3 °C RH = 80% with condensation and 5% imbalance
t = 25 °C RH < 27% t = 5 °C as acc. to EN308
Tab. 7: Temperature ratio for the a³ unit