3 Filling and bleeding
See Installation Quick Guide for more information.
1. Fill the system with cold water by opening the filler valve, that is on the valve pipe, to a pressure of 1 bar.
2. Open all radiator valves fully.
3. Bleed all radiators.
4. Bleed the outdoor unit. See figure 3.
5. Refill the heating system to a pressure of 1 bar.
6. Repeat the procedure until all air has been removed.
7. Check the system for leakage.