Fuse table
Heat pump Heat pump + Immersion Heater Immersion Heater only
3 kW 6 kW 9 kW 3 kW 6 kW 9 kW
400V, 3N~
5 - 17 kW
16 A 20 A 25 A 32 A 6 A 10 A 16 A
400V, 3N~
3 - 12 kW
10 A 16 A 20 A 25 A 6 A 10 A 16 A
Positioning of the outdoor sensor
H
2/3 x H
Recommended location
Unsuitable location
Position the outdoor sensor on the north or north west side of the
house.
Make sure that the outdoor sensor is not placed in direct sun light.
For taller buildings, the sensor should be positioned between the
second and third floors.
The sensor location must not be completely protected from the
wind but not placed in a direct draft.
The outdoor sensor must not be placed on reflective panel walls.
The sensor must be positioned at least 1 m from openings in the
walls which may emit hot air.
If the sensor cable is connected through a pipe, the pipe must be
sealed so that the sensor is not affected by outgoing air.
Commissioning
DHP-H Varius Pro+/DHP-L Varius Pro+
Danfoss Heating Solutions VIJSG202
11

Other manuals for Danfoss DHP-H Varius Pro+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss DHP-H Varius Pro+ and is the answer not in the manual?

Danfoss DHP-H Varius Pro+ Specifications

General IconGeneral
BrandDanfoss
ModelDHP-H Varius Pro+
CategoryHeat Pump
LanguageEnglish

Related product manuals