DKRCI.PS.RP0.D2.02 | 520H7653| 9
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage
The controller can give the following messages:
E1
Error message
Fault in controller
E11 Valve’s actuator temperature outside its range
E15 Cut-out S2 sensor
E16 Shortcircuited S2 sensor
E17 Cut-out  S3 sensor
E18 Shortcircuited S3 sensor
E19
The input signal on terminals 18-19 is outside 
the range.
E20
The input signal on terminals 14-15 is outside 
the range (P0 signal)
A1
Alarm message
High-temperature alarm
A2 Low-temperature alarm
A11 No refrigerant has been selected
Dene input signal on the analog input AIA:
0: no signal,
1: Temperature setpoint. 0-20 mA
2: Temperature setpoint. 4-20 mA
3:  Displacement of superheat reference. 0-20 mA
4:  Displacement of superheat reference. 4-20 mA
o10 0 4 0
Set supply voltage frequency o12 50 Hz 60 Hz 0
Select display for ”normal picture”
(Display the item indicated in parenthesis by 
briey pressing the bottom button) 
1:  Superheat (Temperature)
2:  Valve’s opening degree (Superheat)
3:  Air temperature (Temperature reference)
o17 1 3 1
Manual control of outputs:
OFF: no manual control 
1:  Relay for solenoid valve: select ON
2:  AKV/A output: select ON
3:  Alarm relay activated (cut out)
o18 o 3 O
Working range for pressure transmitter – min. 
value
o20 -1 bar 60 bar -1.0
Working range for pressure transmitter – max. 
value
o21 -1 bar 60 bar 12
(Setting for the function o09, only AKV and TQ)
Set the temperature value or opening degree 
where the output signal must be minimum (0 or 
4 mA)
o27 -70°C 160°C -35
(Setting for the function o09, only AKV and TQ)
Set the temperature value or opening degree 
where the output signal must be maximum (20 
mA)
o28 -70°C 160°C 15
Refrigerant setting
1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  6=R13.  
7=R13b1.  8=R23.  9=R500.  10=R503.  11=R114.  
12=R142b. 13=User dened. 14=R32. 15=R227.  16=R401A.  
17=R507. 18=R402A.  19=R404A. 20=R407C.  21=R407A.  
22=R407B.  23=R410A.  24=R170.  25=R290.  26=R600.  
27=R600a.  28=R744.  29=R1270. 30=R417A. 31=R422A. 
32=R413A. 33=R422D. 34=R427A. 35=R438A
o30 0 35 0
Service
TQ valve's actuator temperature u04 °C
Reference of the valve's actuator temperature u05 °C
Analog input AIA (18-19) u06 mA
Analog output AO (2-5) u08 mA
Read status of input DI u10 on/o
Thermostat cut-in time u18 min.
Temperature at S2 sensor u20 °C
Superheat u21 K
Superheat reference u22 K
Read AKV valve’s opening degree u24 %
Read evaporating pressure u25 bar
Read evaporating temperature u26 °C
Temperature at S3 sensor u27 °C
Temperature reference u28 °C
Read signal at pressure transmitter input u29 mA
*) This setting will only be possible if a data communication module has been 
installed in the controller.