16 Manual RS8FM602 © Danfoss 02-2016 EKC 326A
List of literature
Instructions RI8NG (extract from this manual).
Here you can see how controllers are mounted and
programmed.
Installation guide for extended operation RC8AC
Here you can see how a data communication
connection to ADAP-KOOL® Refrigeration control
systems can be established.
ADAP-KOOL®
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Installation considerations
Accidental damage, poor installation, or site conditions, can give
rise to malfunctions of the control system, and ultimately lead to a
plant breakdown.
Every possible safeguard is incorporated into our products to
prevent this. However, a wrong installation, for example, could still
present problems. Electronic controls are no substitute for normal,
good engineering practice.
Danfoss will not be responsible for any goods, or plant compo-
nents, damaged as a result of the above defects. It is the installer's
responsibility to check the installation thoroughly, and to t the
necessary safety devices.
Error Alarm message ICMTS action (Vhp) ETS action (Vgbp)
EKC supply interrupted none EKC AO remains 0 V – ICMT closes if ICMTS has
battery back-up
No change in opening degree
EKC Standby – Main
Switch OFF
A45 – Standby mode ICMTS closes ETS closes to 'Vgbp OD Min' setting
Sgc interrupted E15 – Sgc o.c. ICMTS regulates with “Emergency cooling” No change – ETS control attempts to maintain
Prec
Sgc short circuited E16 – Sgc s.c. ICMTS regulates with “Emergency cooling” No change – ETS control attempts to maintain
Prec
Pgc transmitter error E20 – Pgc input err ICMTS regulates with “Emergency cooling” No change – ETS control attempts to maintain
Prec
Prec transmitter error E39 – Prec input err No change – ICMTS control continues ETS regulates with “Emergency cooling”
StepMotor error A43 – Step motor err No change – ICMTS control continues ETS closes to 'Vgbp OD Min' setting
Pgc Max limit exceeded A82 – PgcMax alarm No change – ICMTS control attempts to lower
Pgc
No change – ETS control attempts to maintain
Prec
Pgc Min limit exceeded A83 – PgcMin alarm No change – ICMTS control attempts to raise Pgc No change – ETS control attempts to maintain
Prec
Prec Min limit exceeded A84 – PrecMin alarm No change – ICMTS control attempts to maintain
Pgc
No change – ETS control attempts to raise Prec
PgcRef Alarm A94 – PgcRef alarm No change – ICMTS control attempts to maintain
Pgc
No change – ETS control attempts to raise Prec
PrecRef Alarm A95 – PrecRef alarm No change – ICMTS control attempts to maintain
Pgc
No Change – ETS control attempts to raise Prec
EKC HW error E1 – Controller fault No change – ICMTS control continues No change – ETS control continues
"Emergency cooling"
The valve's average opening degree for the last six hours is
regularly saved. This opening degree is used if there is a need for
emergency cooling.
Valve function in alarm situations

Other manuals for Danfoss EKC 326A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKC 326A and is the answer not in the manual?

Danfoss EKC 326A Specifications

General IconGeneral
BrandDanfoss
ModelEKC 326A
CategoryController
LanguageEnglish

Related product manuals