EasyManuals Logo

Danfoss EKC 331T User Manual

Danfoss EKC 331T
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
 EKC 331T  Instructions  RI8GZ353  ©  Danfoss  05/2006  5
ENGLISH
Operation
Menu survey
Light-emitting diodes (LED) on front panel
There are four LEDs on the front panel which will light up  
when the relays are operated.
All LED’s will ash if there is an error in the regulation. In this  
situation you can upload the error code on the display and  
cancel the alarm by pushing the top button briey.
Display
The values will be shown with three digits, and with a setting  
you can determine whether the temperature are to be shown  
in °C or in °F.
The buttons
When you want to change a setting, the two buttons will give 
you a higher or lower value depending on the button you are 
pushing. But before you change the value, you must have 
access to the menu. You obtain this by pushing the upper 
button for a couple of seconds - you will then enter the column 
with parameter codes. Find the parameter code you want to 
change and push the two buttons simultaneously. When you have 
changed the value, save the new value by once more pushing the 
two buttons simultaneously.
Gives access to the menu
 (or cutout an alarm)
Gives access to changes
Saves a change
Examples of operations
Set the regulations set point
1.  Push the two buttons simultaneously
2.  Push one of the buttons and select the new value
3.  Push both buttons again to conclude the setting
Set one of the other menus
1.  Push the upper button until a parameter is shown
2.  Push one of the buttons and nd the parameter you want 
to change
3.  Push both buttons simultaneously until the parameter value 
is shown
4.  Push one of the buttons and select the new value
5.  Push both buttons again to conclude the setting
The controller can give the following messages:
E1
Error message
Errors in the controller
E2
Regulation out of range or control signal is 
defect.
A1
Alarm message
High pressure alarm 
A2 Low pressure alarm
A11 No refrigerant selected
A12
Regulation stopped due to interrupted signal 
on the DI input
Function
Para-
me-
ter
Min. Max.
Factory
setting
Normal display
Shows the signal from the temperature sensor / 
pressure transmitter
-
°C
Reference
Set the regulations set point
-
-60 °C 170 °C 3
Neutral zone r01
0.1 K 20 K 4.0
SW: 1.1x
Max. limitation of set point setting r02
-60 °C 170 °C 50
Min. limitation of set point setting r03
-60 °C 50 °C -60
Correction of signat from the sensor r04
-20 K 20 K 0.0
Select unit (C-b=°C and  F-P= °F) r05
C-b F-P C-b
Reference displacement by signal at DI input r13
-50 K 50 K
0
Capacity
Min. ON time for relays
c01 0 min. 30 min 2
Min. time period between cutins of same relay
c07 0  min. 60 min. 4
Denition of regulation mode
1: Sequential (step mode / FILO)
2: Cyclic (step mode / FIFO)
3: Compressor with unloader
c08 1 3 1
If the regulation mode 3 has been selected, the 
relays for the unloaders can be dened to: 
no: Cut in when more capacity is required
nc: Cut out when more capacity is required
c09 no nc no
Regulation parameter for + Zone
c10 0.1 K 20 K 3
Regulation parameter for + Zone min.
c11 0.1 min. 60 min. 2
Regulation parameter for ++ Zone seconds
c12 1 s 180 s 30
Regulation parameter for - Zone
c13 0 K 20 K 3
Regulation parameter for - Zone min.
c14 0.1 min. 60 min. 1
Regulation parameter for - -  Zone seconds
c15 1 s 180 s
30
Alarm
Alarm time delay
A03 1 min. 90 min. 30
Upper alarm limit (absolute value)
A10 -60 °C 170 °C 50
Lower alarm limit (absolute value)
A11 -60 °C 50 °C
-60
Miscellaneous
Controllers address
o03* 1 60 0
On/o switch (service-pin message)
o04* - - -
Access code
o05 o(-1) 100 -
Dene input signal and application:
0: no signal  / regulation stopped
1: 4-20 mA pressure transmitter - compressor 
reg.
2: 4-20 mA pressure transmitter - condenser reg.
3: AKS 32R pressure transmitter - compressor reg.
4: AKS 32R pressure transmitter - condenser reg.
5: 0 - 10 V relay module
6: 0 - 5 V relay module
7: 5 - 10 V relay module
8: Pt 1000 ohm sensor - compressor reg.
9: Pt 1000 ohm sensor - condenser reg.
10: PTC 1000 ohm sensor - compressor reg.
11: PTC 1000 ohm sensor - condenser reg.
o10 0 11 0
Set supply voltage frequency
o12 50 Hz 60 Hz 50
Manual operation with “x” relays
o18 0 4 0
Dene number of relay outputs
o19 1 4 4
Pressure transmitter’s working range - min. value
o20 -1 bar 0 bar -1
Pressure transmitter’s working range - max. value
o21 1 bar 40 bar
12
Dene DI input:
0: not used
1: Contact displaces reference
2: Contact starts and stops regulation
3: Interrupted contact will cut out the capacity, 
and alarm will be given.
o22 0 3 0
Operating hours of relay 1 (value times 10)
o23 0 h 999 h 0
Operating hours of relay 2 (value times 10)
o24 0 h 999 h 0
Operating hours of relay 3 (value times 10)
o25 0 h 999 h 0
Operating hours of relay 4 (value times 10)
o26 0 h 999 h 0
Setting of refrigerant
1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  
6=R13.  7=R13b1.  8=R23.  9=R500.  10=R503.  
11=R114.  12=R142b. 13=User dened. 14=R32. 
15=R227.  16=R401A.  17=R507. 18=R402A.  
19=R404A. 20=R407C.  21=R407A.  22=R407B.  
23=R410A.  24=R170.  25=R290.  26=R600.  
27=R600a.  28=R744.  29=R1270.  30=R417A
o30 0 30 0
*) This setting will only be possible if a data communication moduel has been 
installed in the controller.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKC 331T and is the answer not in the manual?

Danfoss EKC 331T Specifications

General IconGeneral
BrandDanfoss
ModelEKC 331T
CategoryController
LanguageEnglish

Related product manuals