VLT
®
5000 SyncPos option
MG.10.J4.02 – VLT is a registered Danfoss trade mark
92
Software Reference
MOTOR OFF
The motor control can be disabled by using the
MOTOR OFF command. After MOTOR OFF, the
drive axis can be moved freely, as long as there is
no motor brake. A monitoring of the actual position
will continue to take place, i.e. the actual position
(APOS) can still be queried after MOTOR OFF.
NB!
For a restart of a motion process after
MOTOR OFF the command MOTOR ON
must be used. Only the command ERRCLR auto-
matically activates MOTOR ON.
Summary
turns off motor control
Syntax
MOTOR OFF
Command group
INI
Cross Index
MOTOR ON
Syntax-Example
MOTOR OFF
/* switch off controller of the axis */
Program sample
MOTOR_01.M
POS_01.M
MOTOR ON
The motor control can be enabled again, following
a previous MOTOR OFF, by use of the MOTOR ON
command. When carrying out the MOTOR ON, the
commanded position is set to the actual position,
i.e. the motor remains at the actual position. Thus
the positioning error is reset at the execution of
MOTOR ON.
Summary
turns on motor control
Syntax
MOTOR ON
NB!
The MOTOR ON command is not suitable
for re-activation of position control following
an error. For this purpose, the ERRCLR command
is to be used.
Command group
INI
Cross Index
MOTOR OFF
Syntax-Example
MOTOR ON
/* switch on controller of the axis */
Program sample
MOTOR_01.M
POS_01.M