Immunity continued
Basic standard Burst
IEC 61000-4-4
Surge
IEC 61000-4-5
ESD
IEC 61000-4-2
Radiated electromagnetic field
IEC 61000-4-3
Mains
distortion
VDE 0160
RF common
mode voltage
IEC 61000-4-6
Acceptance criterion B B B A A
Port connection CM DM CM CM CM
Line OK OK OK OK
Motor OK OK
Control lines OK OK OK
Application and Fieldbus options OK OK OK
Signal interface<3 m OK
Enclosure OK OK OK
Load sharing OK OK
Standard bus OK OK OK
Brake OK OK
External 24 V DC OK OK OK
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
VLT
®
5000 Design Guide
126 MG.52.B2.02 - VLT
®
is a registered Danfoss trademark