Installation Guide
VLT®Safety Option MCB 152
VLT® AutomationDrive FC 302 and VLT® Decen-
tral Drive FCD 302

Table of Contents

Questions and Answers

  • J
    Jerry WilliamsAug 15, 2025
    Why Danfoss VLT Safety Option MCB 152 show External error: Safe field-bus telegram mismatch?
    • E
      Eric SmithAug 15, 2025
      If your Danfoss DC drive displays the 'External error: Safe field-bus telegram mismatch' error, it means the safe fieldbus telegram is invalid. To resolve this, check the telegram format settings in both the fail-safe PLC and the safety option.
  • M
    Mark DodsonAug 18, 2025
    What to do if Danfoss VLT Safety Option MCB 152 show External error: Safe field-bus destination address mismatch?
    • T
      thompsonjamesAug 18, 2025
      If you encounter the 'External error: Safe field-bus destination address mismatch' error on your Danfoss DC drive, it indicates that the destination address on the safe fieldbus is invalid. Ensure that the addresses on the PLC and the safety option match to correct this issue.
  • C
    Colin ValenzuelaAug 21, 2025
    What to do if Danfoss VLT Safety Option MCB 152 DC Drives show Internal error: Fail-safe data CRC mismatch?
    • K
      Kayla WatsonAug 21, 2025
      If your Danfoss DC drive displays the error 'Internal error: Fail-safe data CRC mismatch', this means the CRC of the safety option does not match the stored CRC value on the drive. To solve this, configure the safety option with MCT 10 Safe Plug-in or by CRC select/LCP copy.
  • K
    Kevin MillerAug 25, 2025
    What to do if Danfoss VLT Safety Option MCB 152 DC Drives show External error DI1?
    • M
      Melissa MarshallAug 25, 2025
      If your Danfoss DC drive is showing 'External error DI1', it could be due to a safety input connected to DI1 having an illegal signal level, or the sensor might be broken. You can resolve this by checking that the configuration of DI1 (parameter 42-21 Type, sub-index [0]) is set correctly and that the connected sensor is installed according to specification. Additionally, you can extend the discrepancy time for DI1 using the VLT® Motion Control Tool MCT 10 Safe Plug-in.
  • B
    Briana CabreraAug 27, 2025
    What to do if Danfoss VLT Safety Option MCB 152 show External error DI2?
    • E
      Emily JonesAug 27, 2025
      If your Danfoss DC drive displays 'External error DI2', this could be caused by a safety input connected to DI2 having an illegal signal level, or the sensor may be broken. To fix this, check that the configuration of DI2 (parameter 42-21 Type, subindex [0]) is set correctly and that the connected sensor is installed according to specification. You might also need to extend the discrepancy time for DI2 using the VLT® Motion Control Tool MCT 10 Safe Plug-in.
  • C
    Christina McconnellAug 30, 2025
    What to do if Danfoss VLT Safety Option MCB 152 show Internal error: DI1 in PUST?
    • S
      Sarah StephensonAug 30, 2025
      If your Danfoss DC drive shows the error 'Internal error: DI1 in PUST', it indicates that the safety input connected to DI1 has illegal signal levels, or the sensor is broken. To resolve this, check that the configuration of DI1 (parameter 42-21 Type, sub-index [0]) is set correctly and that the connected sensor is installed according to specification. You can also extend the discrepancy time on the safe input using the VLT® Motion Control Tool MCT 10 Safe Plug-in.
  • T
    Tommy AyalaSep 2, 2025
    What to do if Danfoss VLT Safety Option MCB 152 DC Drives show Internal error: DI2 in PUST?
    • J
      Jaime HannaSep 2, 2025
      If your Danfoss DC drive displays the error 'Internal error: DI2 in PUST', it means that the safety input connected to DI2 has illegal signal levels, or the sensor is broken. To fix this, check that the configuration of DI2, parameter 42-21 Type, is set correctly or that the connected sensor is installed according to specification. You can also extend the discrepancy time on the safe input using the VLT® Motion Control MCT 10 Safe Plug-in.
  • M
    Melanie StewartSep 5, 2025
    How to fix Internal error: No CAN communication on Danfoss VLT Safety Option MCB 152?
    • J
      James Wang MDSep 5, 2025
      To address the 'Internal error: No CAN communication' on your Danfoss DC Drive, try the following actions: * Power cycle the drive. * Restart the safety option via parameter 42-90 Restart Safe Option.
  • A
    Amanda FlemingSep 8, 2025
    How to fix Internal error: Processor error on Danfoss DC Drives?
    • B
      Brett WellsSep 8, 2025
      To fix the 'Internal error: Processor error' on your Danfoss DC Drive, you can try the following: * Power cycle the drive. * Restart the safety option via parameter 42-90 Restart Safe Option.
  • L
    Leon YoungSep 12, 2025
    How to fix Internal error: Safe output switch 2 on Danfoss DC Drives?
    • J
      Jennifer SimmonsSep 12, 2025
      To resolve the 'Internal error: Safe output switch 2' on your Danfoss DC drive, check that the configuration of output switch 2 is set correctly.

Summary

Safety

Qualified Personnel

Specifies requirements for personnel performing installation and maintenance.

Protective Measures

Lists essential measures for safe installation and operation.

Safety Precautions

Highlights critical safety warnings for high voltage and unintended starts.

Risk Assessment

Guides on performing risk assessments for safety-related systems.

Functions

Safe Torque Off - STO

Details the STO safety subfunction and its behavior.

Installation

Safety Instructions

Crucial safety guidelines for drive and option installation.

Installing the Option

Step-by-step guide for physically installing the safety option.

Electrical Installation

Covers wiring requirements and procedures for electrical connections.

Commissioning

Before Commissioning

Prerequisites and site preparation for commissioning.

Commissioning Procedure

Outlines the steps for commissioning the safety option.

Commissioning Test

Explains how to validate safety functions after configuration.

Configuring the Safety Option

PROFIsafe Configuration

Guides on setting up PROFIsafe communication.

Configuring PROFIsafe with Siemens Step 7

Step-by-step guide for Siemens Step 7 integration.

Parameter Setup

Maintenance, Diagnostics, and Troubleshooting

Repair and Troubleshooting

Covers procedures for removing, replacing, and troubleshooting the option.

Error Conditions

Explains different error types and their effects.